InteliSys NTC BaseBox
Premium and Cogeneration (CHP) Gen-set Controller
FeaturesPremium gen-set controller for both single and multiple gensets operating in standby or parallel modes
Support of cogeneration (CHP) and other complex applications
To be used in conjunction with detachable colour displays InteliVision 8 or InteliVision 5
Support of engines with ECU (Electronic Control Unit)
Complete integrated gen-set solution and signal sharing via CAN bus – minimum external components needed
Many communication options – easy remote supervising and servicing
Gen-set performance log for easy problem tracing
Automatic synchronizing and power control (via speed governor or ECU)
Baseload, Import / Export, TempByPower, Peak shaving, Voltage and PF control (AVR)
Generator measurement: U, I, Hz, kW, kVAr, kVA, PF, kWh, kVAhr
Mains measurement: U, I, Hz, kW, kVAr, PF
Selectable measurement ranges for AC voltages and currents – 120 / 277 V, 0–1 / 0–5 A
Inputs and outputs configurable for various customer needs
Bipolar binary output – possibility to use BO as High or Low side switch
1× RS232 / 2× RS485 interface with Modbus protocol support; Analog / GSM / ISDN / CDMA modem communication support; SMS messages; ECU
Modbus interface; secondary RS485 converter is isolated
AirGate support
Ethernet connection (RJ45)
USB 2.0 slave interface
Event-based history (up to 4000 records) with customer-selectable list of stored values; RTC; statistic values
Pre mortem history (50 records)
Integrated PLC programmable functions
Integrated fixed and configurable protections
Customized firmware solution
InteliSys NTC BaseBox Controller/Function Chart |
Order code |
IS-NTC-BB |
Binary Inputs / Outputs |
16/16 (112/112) 1) |
Analog Inputs/Outputs |
4/1 (84/33) 1) (configurable as tristate) |
AMF function |
• |
GCB control with feedback |
• |
Integrated PLC |
Extended |
Input configuration |
• |
Output configuration |
• |
Voltage measurement Gen / Mains (bus) |
3 ph / 3 ph 120V / 277V |
Current measurement |
3ph + 1 / 6w IDMT overcurrent 1A / 5A |
kW / kWh / kVA measurement |
•/•/• |
Communication interfaces |
CAN1, CAN2, RS232, 2× RS485, USB, Ethernet, Modbus, Modbus TCP, AirGate, Web server |
ECU support |
• |
Active call / SMS support |
• |
Forward / Reverse synchronizing / Mains parallel operation |
•/•/• |
Multiple operation / Power Management System |
•4) |
Display |
External |
History (max records)5) |
4000 |
Notera:KEY • included
CAN1 for peripheral modules and ECU (J1939)
CAN2 intercontroller can; monitoring
1) With IS-AIN8, IS-AIN8TC, IS-BIN16/8, I-OUT8 or IGS-PTM
2) More PLC blocks are available with IGS–NT–miniCHP dongle
3) With communication modules
4) With IGS-NT-LSM+PMS dongle
5) Depends on number of values in history record
»
Click here to see image»
InteliSys NTC BaseBox Product Leaflet »
InteliMains NTC Basbox schematic diagram »
InteliMains NTC Basbox schematic Application diagram