GREENPOWER Perkins Diesel Power generator 450kVA 360kW Open frame Manual starting
Greenpower Equipped with water-cooled Perkins diesel engine. Supplied with stable framework and Green Power electrical panel, voltmeter, frequency meter, ammeter, hour meter, starter key and indicator panel for oil, battery charge and low fuel level. As an option, we also supply the silenced version.
Specification
- Prime running power (PRP) 450kVA, 360kW
- Emergency stand by power (ESP) 495kVA, 396 kW
- 400/230 V @ 50 Hz 1500 rpm
- High quality and reliable 6-cylinder Perkins diesel engine
- Easily operated control panel
- Brushless permanent magnetized generator IP23 with optional electronic AVR
- 400 liter fuel tank with leakage protection
» Click Here to view the Engine Datasheet
» Click here to see Datasheet
Technical Data | |
Generator EngineGenerator Engine | Perkins 2506A-E15TAG1 |
Type | 4 cycle, water-cooled, diesel engine |
Compression Ratio | 16:1 |
No of Cylinders | 6 |
Cylinders Arrangement | In-line |
Displacement | 15.2 Liters |
Bore x Stroke | 137 x 171 mm |
Prime running power (PRP) | 450 kVA/360 kW |
Emergency stand by power (ESP) | 495 kVA/396 kW |
Speed | 1500 rpm |
Governor | Electronic |
Fuel Consumption | 72 liter/hour |
Rated Current | 800 Amps |
Rated Voltage | 400V/230V |
Landuse Type of Unit | Low Noise, Automation Type |
Weight | 4200 Kg |
Dimension (LxBxH) | 3450x1550x2100 mm |
Rotation | Anti-clockwise |
Fuel tank | 400liter with leakage protection |
Standard tank capacity | 400 l |
Current | 649A |
Sound level | 69dB (A) |
Frequency | 50Hz |
Motor power |
531/396 (hp/kW) |
Standard equipment | Other configurations |
|
|
Accessories |
|
|
- Perkins heavy duty diesel engine
- 6 cylinder equipped with Water cooling
- Mechanical governor control system
- Replaceable wet type cylinder liners
- Replaceable fuel filter, oil filter and dry element air filter
- Cooling radiator and fan
- Fuel connection hoses and manual sump oil drain valve
- Exhaust silencer
- Maintenance free battery including rack and cables
- Jacket water heater (as option)
- Perkins Engine Manual
- Brushless, single bearing system
- Insulation class H with circuit breaker protection
- Standard degree of protection IP 23
- Self-exciting and self-regulating
- Main line circuit breaker
- Close voltage regulation
Greenpower AB reserves the right to make any errors or changes in specifications. © Copyright / Greenpower AB.