GREENPOWER Perkins Diesel Power generator 10kVA 8kW Open frame Manual starting
Greenpower Equipped with stable framework, Green Power electrical panel, voltmeter, frequency meter, ampere meter, hour meter, key switch and indicator panel for the oil, battery charging and low fuel level. As an option, we also produce the silenced version.
Specification
- Prime running power (PRP) 10kVA, 8kW
- Emergency stand by power (ESP) 11kVA, 8.8 kW
- 400/230 V @ 50 Hz 1500 rpm
- High quality and reliable 3-cylinder Perkins diesel engine
- Easy to operate control panel
- Brushless permanent magnetized generator IP23 with optional electronic AVR
- Fuel tank 50 liters with leakage protection
» Click Here to view the Engine Datasheet
» Click here to see Datasheet
Technical data | |
Generator Engine | Perkins 403A-11G |
Type | 4 cycle, water-cooled, diesel engine |
Compression Ratio | 23:1 |
No of Cylinders | 3 |
Cylinders Arrangement | In-line |
Displacement | 1.131 Liters |
Bore x Stroke | 77 x 81 mm |
Prime running power (PRP) | 10 kVA/8 kW |
Emergency stand by power (ESP) | 11 kVA/8.8 kW |
Speed | 1500 rpm |
Mechanical output | 8-9 kWm |
Fuel Consumption | 2.3 liter/hour |
Rated Current | 25 Amps |
Rated Voltage | 400V/230V |
Landuse Type of Unit | Low Noise, Automation Type |
Engine power, 1500 rpm | 89 kW |
Rotation | Anti-clockwise |
Dimension (LxBxH) | 1400x700x1400 mm |
Weight | 360 Kg |
Sound level | 68dB (A) |
Standard tank capacity | 50 l |
Frequency | 50Hz |
Motor power | 11.3/8.4(hp/kW) |
Fuel tank | 55liter with leakage protection |
Standard equipment | Other configurations |
|
|
Accessories |
|
|
Engine
- Perkins heavy duty diesel engine
- Three cylinder equipped with Water cooling
- Mechanical governor control system
- Replaceable wet type cylinder liners
- Replaceable fuel filter, oil filter and dry element air filter
- Cooling radiator and fan
- Fuel connection hoses and manual sump oil drain valve
- Exhaust silencer
- Maintenance free battery including rack and cables
- Jacket water heater (as option)
- Perkins Engine Manual
- Brushless, single bearing system
- Insulation class H with circuit breaker protection
- Standard degree of protection IP 23
- Self-exciting and self-regulating
- Main line ciucuit breaker
- Close voltage regulation
Greenpower AB reserves the right to make any errors or changes in specifications. © Copyright / Greenpower AB.